Installer Setup (ISU)


Installer Options

S200 Smart thermostats can be set up using the Resideo Pro app:

S200 Smart thermostats can be set up using the Resideo Pro app. Touch the icon below to download the Resideo Pro app:

For S200 Smart models: After initial setup is complete, the thermostat will ask if you wish to perform setup on the device or by using the app.

If you select Using App open the Resideo Pro app and follow the instructions.

If you choose On Device follow the steps outlined below in the next section "Configure the Thermostat".

If entering the installer menu after initial setup, follow the steps below:

  1. Press and hold the bottom left button and Up arrow button for 5 seconds to access INSTALLER MENU.

  2. Press or to cycle through INSTALLER MENU options. When the menu option you want to adjust is displayed, press SELECT.

Installer Menu Options

  • ISU- Installer Setup options.

  • TEST- Installer Test options.

  • INFO- Displays a code used by the Resideo technical support team when needed.

  • RSET- Reset options. Reset Schedule, WiFi (S200) or Perform A Factory Reset.

  • REV- STAT: Displays thermostat's Firmware version. WiFi: Displays WiFi version.

To return to the Home screen, press the EXIT button (upper left) or wait for the thermostat to time out.


Configure the Thermostat

On initial setup, the thermostat will go to the ISU menu. S200 models will ask if you wish to perform setup on the device or by using the app. If entering the ISU menu on the device after initial setup, follow the steps below:

  1. Press and hold the bottom left button and Up arrow button for 5 seconds to access the INSTALLER MENU.

  2. Press or to cycle through INSTALLER MENU options. When ISU is displayed, press SELECT.

  3. The display shows the ISU number on the left and the ISU setting on the right.

    When an ISU number is displayed, press or to change the setting for that ISU.

  4. After choosing the correct setting for an ISU, press NEXT to advance to the next ISU setting.

  5. To finish setup, press the SAVE & EXIT button; this will save your settings and return to the Home screen.


Installer Setup Options (ISU)

Note: Depending on system settings, not all options may be available.

# ISU

ISU Name

ISU Options (factory defaults are bold)

1040

Scheduling options (Schedule can be turned on or off by the user under Menu > Schedule)

1 = 1 week (all days the same)

2 = 5-2 Programmable (separate weekdays and weekend)

3 = 5-1-1 Programmable (separate Saturday and Sunday)

4 = 7-Day Programmable (each day separate)

1050

Temperature Indication Scale

F = Fahrenheit

C = Celsius

1060

Outdoor Sensor (TH2320 models only)

0 = None

1 = Wired Outdoor Sensor

2 = Internet Weather (TH2320WF)

2000

Heating System Type

1 = Conventional Forced Air Heat

2 = Heat Pump

3 = Radiant Heat

5 = None (Cool Only)

2010

Heating Equipment Type

Conventional Forced Air Heat:

1 = Standard Efficiency Gas Forced Air

2 = High Efficiency Gas Forced Air

3 = Oil Forced Air

4 = Electric Forced Air

5 = Hot Water Fan Coil

 

Heat Pump:

7 = Air to Air Heat Pump

8 = Geothermal Heat Pump

 

Radiant Heat:

9 = Hot Water Radiant Heat

12 = Steam

2060

Reversing Valve O/B

0 = O (O/B in Cool)

1 = B (O/B in Heat)

2070

Compressor Stages

0, 1, 2

Note: Only 1 compressor stage available on TH2110 models

2071

Heat Stages / Backup Heat Stages

Heat Stages: 1, 2

Backup Heat Stages: 0, 1 (TH2320 models only)

2110

Fan Control in Heat
(Only shown if 2010 = 4 or 5)

1 = Equipment Controls Fan

2 = Thermostat Controls Fan

2175

Aux/E terminal control
(TH2320 models only)

0 = Drive both Aux & E together

1 = Aux and E independent

2180

Backup Heat Source (Heat Pump Only)
(TH2320 models only)

31 = Electric Forced Air

32 = Standard Efficiency Gas Forced Air

33 = High Efficiency Gas Forced Air

34 = Oil Forced Air, Hot Water Fan Coil

36 = Hot Water Radiant Heat

2185

Emergency Heat Source
(TH2320 models only)

3000

System Changeover

0 = Manual

1 = Automatic

3015

Auto Changeover Differential

0 °F to 5 °F

0.0 °C to 2.5 °C

Note: The Differential setting is the minimum number of degrees from set-point needed to switch from the last mode running (Heat or Cool) to the opposite mode when the thermostat is in auto-changeover.

3020

Finish With High Heat Stage

0 = No

1 = Yes

Note: TH2320 models only.

3021

Finish With High Cool Stage

0 = No

1 = Yes

Note: TH2320 models only.

3090

Backup Heat Droop

[0] = Comfort

2 °F to 15 °F (in 1 °F increments)
1.0 °C to 7.5 °C (in 0.5 °C increment)

Note: 0 (comfort) setting only available if Backup Heat (ISU 2180) is set to Electric. (TH2320 only)

3110

Upstage Timer for Backup Heat (If 3090 = 0 and 2180 = 31, 3110 only has settings 0-3)

0 = Off

1 = 30 minutes

2 = 45 minutes

3 = 60 minutes

4 = 75 minutes

5 = 90 minutes

6 = 2 hours

7 = 3 hours

8 = 4 hours

9 = 5 hours

10 = 6 hours

11 = 8 hours

12 = 10 hours

13 = 12 hours

14 = 14 hours

15 = 16 hours

3120

Compressor Lockout / Balance Point (TH2320 models only) (1060 needs to be set to 1 or 2)

Off

-15°F to 60°F (in 5°F increments)

-26.0°C to 15.5°C (in 2.5°C or 3.0°C increments)

3121

Outdoor Lockout Backup Heat

(TH2320 models only)

Off

5 °F to 65 °F (in 5 °F increments)

-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)

3125

Lockout Fan after a Cool call

[0] = Off

1 = 5 min

2 = 10 min

3 = 15 min

4 = 20 min

5 = 25 min

6 = 30 min

7 = 35 min

8 = 40 min

9 = 45 min

10 = 50 min

11 = 55 min

12 = 60 min

13 = 65 min

14 = 70 min

15 = 75 min

16 = 80 min

17 = 85 min

18 = 90 min

19 = 95 min

20 = 100 min

21 = 105 min

22 = 110 min

23 = 115 min

24 = 120 min

3140

Compressor Cycle Rate (Stage 1)

1 - 6

3141

Compressor Cycle Rate (Stage 2)

1 - 6 (TH2320 models only)

3150

Heating Cycle Rate (Stage 1)

1 - 12

3151

Heating Cycle Rate (Stage 2)

1 - 12 (TH2320 models only)

3160

Heating Cycle Rate Auxiliary Heat

1 - 12 (TH2320 models only)

3165

Heating Cycle Rate Emergency Heat

1 - 12 (TH2320 models only)

3240

Compressor Protection

0 = Off

1 - 5 minutes

4090

Adaptive Intelligent Recovery

0 = No

1 = Yes

Note: Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.

4100

Maximum Cool Setpoint

90 °F to 99 °F (99 °F)
32.0 °C to 37.0 °C (37.0 °C)

4101

Minimum Cool Setpoint

50 °F to 99 °F (50 °F)
10.0 °C to 37.0 °C (10.0 °C)

4102

Maximum Heat Setpoint

32 °F to 90 °F (90 °F)
4.5 °C to 32.0 °C (32.0 °C)

4103

Minimum Heat Setpoint

32 °F to 90 °F (40 °F)
0 °C to 32.0 °C (4.5 °C)

4110

Keypad Lockout

0 = Disabled

1 = Enabled

7020

Number of Air Filters

0 - 2

7110

Air Filter 1 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 = 45 Calendar Days

11 = 60 Calendar Days

12 = 75 Calendar Days

13 = 3 Calendar Months

14 = 4 Calendar Months

15 = 5 Calendar Months

16 = 6 Calendar Months

17 = 9 Calendar Months

18 = 12 Calendar Months

19 = 15 Calendar Months

7111

Air Filter 2 Replacement Reminder

14003

Backlighting

0 = On Demand

1 = Continuous

Note: Common wire needed for continuous.

14004

Backlight brightness

1 - 5

Note: Only displayed if Continuous backlight selected.

14005

Idle screen selection

0 - Minimum Information shown

1 - Setpoint shown on idle screen

2 - Maximum display information shown

14006

Idle screen message center (WiFi Models only)

Note: When ISU 1060 = 1, the outdoor temperature can be viewed on device under MENU, then TEMP

1 - Time

2 - Outdoor Temp (ISU 1060 = Internet, Wired)

3 - Outdoor Humidity (ISU 1060 = Internet)

4 - Indoor Humidity

14007

Home screen message center (WiFi Models only)

Note: When ISU 1060 = 1, the outdoor temperature can be viewed on device under MENU, then TEMP

14010

Clock Format

12 / 24

14015

Daylight Saving Time

0 = Off

1 = On

14020

Temperature Display Offset

-3 °F to 3 °F (0)
-1.5 °C to 1.5 °C (0)

ISU#: 1040

Scheduling options (Schedule can be turned on or off by the user under Menu > Schedule)

1 = 1 week (all days the same)

2 = 5-2 Programmable (separate weekdays and weekend)

3 = 5-1-1 Programmable (separate Saturday and Sunday)

4 = 7-Day Programmable (each day separate)

ISU#: 1050

Temperature Indication Scale

F = Fahrenheit

C = Celsius

ISU#: 1060

Outdoor Sensor (TH2320 models only)

0 = None

1 = Wired Outdoor Sensor

2 = Internet Weather (TH2320WF)

ISU#: 2000

Heating System Type

1 = Conventional Forced Air Heat

2 = Heat Pump

3 = Radiant Heat

5 = None (Cool Only)

ISU#: 2010

Heating equipment type

Conventional Forced Air Heat:

1 = Standard Efficiency Gas Forced Air

2 = High Efficiency Gas Forced Air

3 = Oil Forced Air

4 = Electric Forced Air

5 = Hot Water Fan Coil

 

Heat Pump:

7 = Air to Air Heat Pump

8 = Geothermal Heat Pump

 

Radiant Heat:

9 = Hot Water Radiant Heat

12 = Steam

ISU#: 2060

Reversing Valve O/B

0= O (O/B in Cool)

1=B (O/B in Heat)

ISU#: 2070

Compressor Stages

0, 1, 2

Only 1 compressor stage available on TH2110 models

ISU#: 2071

Heat Stages/Backup Heat Stages

Heat Stages: 1, 2

Backup Heat Stages: 0, 1 (TH2320 models only)

ISU#: 2110

Fan Control in Heat (Only shown if 2010 = 4 or 5)

1 = Equipment Controls Fan

2 = Thermostat Controls Fan

ISU#: 2175

Aux/E terminal control (TH2320 models only)

0 = Drive both Aux & E together

1 = Aux and E independent

ISU#: 2180

Backup Heat Source (Heat Pump Only) (TH2320 models only)

31 = Electric Forced Air

32 = Standard Efficiency Gas Forced Air

33 = High Efficiency Gas Forced Air

34 = Oil Forced Air, Hot Water Fan Coil

35 = Hot Water Radiant Heat

36 = Other

ISU#: 2185

Emergency Heat Source (TH2320 models only)

31 = Electric Forced Air

32 = Standard Efficiency Gas Forced Air

33 = High Efficiency Gas Forced Air

34 = Oil Forced Air, Hot Water Fan Coil

35 = Hot Water Radiant Heat

36 = Other

ISU#: 3000

System Changeover

0 = Manual

1 = Automatic

ISU#: 3015

Auto Changeover Differential

0 °F to 5 °F

0.0 °C to 2.5 °C

The Differential setting is the minimum number of degrees

from set-point needed to switch from the last mode running

(Heat or Cool) to the opposite mode when the thermostat is

in auto-changeover.

ISU#: 3020

Finish With High Heat Stage

0 = No

1 = Yes

(TH2320 models only)

ISU#: 3021

Finish With High Cool Stage

0 = No

1 = Yes

(TH2320 models only)

ISU#: 3090

Backup Heat Droop

[0] = Comfort

2 °F to 15 °F (in 1 °F increments)

1.0 °C to 7.5 °C (in 0.5 °C increment)

0 (comfort) setting only available if Backup Heat (ISU 2180) is set to Electric. (TH2320U4006 only)

ISU#: 3110

Upstage Timer for Backup Heat (If 3090 = 0 and 2180 = 31, 3110 only has settings 0-3)

0 = Off

1 = 30 minutes

2 = 45 minutes

3 = 60 minutes

4 = 75 minutes

5 = 90 minutes

6 = 2 hours

7 = 3 hours
8 = 4 hours

9 = 5 hours

10 = 6 hours

11 = 8 hours

12 = 10 hours

13 = 12 hours

14 = 14 hours

15 = 16 hours

ISU#: 3120

Compressor Lockout / Balance Point (TH2320 models only) (1060 needs to be set to 1 or 2)

0 = Off

5 °F to 65 °F (in 5 °F increments)

-15.0 °C to 18.5 °C (in 2.5 °C and 3.0 °C

increments)

ISU#: 3121

Outdoor Lockout Backup Heat (TH2320 models only)

-- = Off

5 °F to 65 °F (in 5 °F increments)

-15.0 °C to 18.5 °C (in 2.5 °C and 3.0 °C

increments)

ISU#: 3125

Lockout Fan after a Cool call

[0] = Off

1 = 5 min

2 = 10 min

3 = 15 min

4 = 20 min

5 = 25 min

6 = 30 min

7 = 35 min

8 = 40 min
9 = 45 min

10 = 50 min

11 = 55 min

12 = 60 min

13 = 65 min

14 = 70 min

15 = 75 min

16 = 80 min
17 = 85 min

18 = 90 min

19 = 95 min

20 = 100 min

21 = 105 min

22 = 110 min

23 = 115 min

24 = 120 min

ISU#: 3140

Compressor Cycle Rate (Stage 1)

1 – 6

ISU#: 3141

Compressor Cycle Rate (Stage 2)

1 – 6 (TH2320 models only)

ISU#: 3150

Heating Cycle Rate (Stage 1)

1 – 12

ISU#: 3151

Heating Cycle Rate (Stage 2)

1 – 12 (TH2320 models only)

ISU#: 3160

Heating Cycle Rate Auxiliary Heat

1 – 12 (TH2320 models only)

ISU#: 3165

Heating Cycle Rate Emergency Heat

1 – 12 (TH2320 models only)

ISU#: 3240

Compressor Protection

0 = Off

1 - 5 minutes

ISU#: 4090

Adaptive Intelligent Recovery

0 = No

1 = Yes

Adaptive Intelligent Recovery (AIR) is a comfort setting. Heating or cooling equipment will turn on earlier, ensuring the indoor temperature will match the setpoint at the scheduled time.

ISU#: 4100

Maximum Cool Setpoint

90 °F to 99 °F (99 °F)
32.0 °C to 37.0 °C (37.0 °C)

ISU#: 4101

Minimum Cool Setpoint

50 °F to 99 °F (50 °F)
10.0 °C to 37.0 °C (10.0 °C)

ISU#: 4102

Maximum Heat Setpoint

32 °F to 90 °F (90 °F)
4.5 °C to 32.0 °C (32.0 °C)

ISU#: 4103

Minimum Heat Setpoint

32 °F to 90 °F (40 °F)
0 °C to 32.0 °C (4.5 °C)

ISU#: 4110

Keypad Lockout

0 = Disabled

1 = Enabled

ISU#: 7020

Number of Air Filters

0 - 2

ISU#: 7110

Air Filter 1 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 =45 Calendar Days

11 =60 Calendar Days

12 =75 Calendar Days

13 =3 Calendar Months

14 =4 Calendar Months

15 =5 Calendar Months

16 =6 Calendar Months

17 =9 Calendar Months

18 =12 Calendar Months

19 =15 Calendar Months

ISU#: 7111

Air Filter 2 Replacement Reminder

0 = Off

1 = 10 Run Time Days

2 = 20 Run Time Days

3 = 30 Run Time Days

4 = 45 Run Time Days

5 = 60 Run Time Days

6 = 90 Run Time Days

7 = 120 Run Time Days

8 = 150 Run Time Days

9 = 30 Calendar Days

10 =45 Calendar Days

11 =60 Calendar Days

12 =75 Calendar Days

13 =3 Calendar Months

14 =4 Calendar Months

15 =5 Calendar Months

16 =6 Calendar Months

17 =9 Calendar Months

18 =12 Calendar Months

19 =15 Calendar Months

ISU#: 14003

Backlighting

0 = On Demand

1 = Continuous

Common wire needed for Continuous.

ISU#: 14004

Backlight brightness

1 - 5

Only displayed if Continuous Backlight selected.

ISU#: 14005

Idle screen selection

0 - Minimum Information shown

1 - Setpoint shown on idle screen

2 - Maximum display information shown

ISU#: 14006

Idle screen message center (WiFi Models only) Note: When ISU 1060 = 1, the outdoor temperature can be viewed on device under MENU, then TEMP

1 - Time

2 - Outdoor Temp (ISU 1060 = Internet, Wired)

3 - Outdoor Humidity (ISU 1060 = Internet)

4 - Indoor Humidity

ISU#: 14007

Home screen message center (WiFi Models only) Note: When ISU 1060 = 1, the outdoor temperature can be viewed on device under MENU, then TEMP

1 - Time

2 - Outdoor Temp (ISU 1060 = Internet, Wired)

3 - Outdoor Humidity (ISU 1060 = Internet)

4 - Indoor Humidity

ISU#: 14010

Clock format

12/24

ISU#: 14015

Daylight Saving Time

0 = Off

1 = On

ISU#: 14020

Temperature Display Offset

-3 to 3 °F (0)

-1.5 to 1.5 °C (0)


Video: Configure ISU Settings

Watch this video to see how to configure ISU settings on the FocusPRO P200 and S200 thermostats


Video: Lock out fan after call for Cool

Watch this video to understand the importance of using the fan lockout feature after a cooling call and learn how to configure it on the FocusPRO P200 & S200 Series Thermostats.


Video: Control Options for Heat Pump Applications on the FocusPRO P200 & S200 Series Thermostats

Watch this video to explore the control options available for heat pump applications on the FocusPRO P200 & S200 Series Thermostats.